TITLE: FIRE TESTING

 

SUMMARY OF TEST RESULTS

Wall System: Exterior Non-load-bearing Wall Assembly

Combustible Components: CL-Talon® Cladding Support System, Estolga® 3000 Rainscreen System, Cladiators® Calor® ACM, Kingspan Kooltherm® K15 Insulation®, and STS coatings.

 

NFPA 285 Test Results

The assembly described and tested in this report did meet the Conditions of Acceptance of NFPA 285. Construction of the full assembly is summarized in Section 7 of this report. Report upon request.

 

TEST REQUIREMENTS TEST RESULTS PASS/FAIL
Flames did not reach 10 ft. above the window opening header. Flames did not reach 10 ft. above the window opening header. PASS
Flames did not reach a lateral distance of 5 ft. from the vertical centerline. Flames did not reach a lateral distance of 5 ft. from the vertical centerline. PASS
Flames did not propagate beyond the limits of the first story test room. Flames did not propagate beyond the limits of the first story test room. PASS
TC's 11 and 14-17 (1000℉ limit) TC's 11 and 14-17 did not exceed their 1000℉ limit. PASS
TC's 18-19, 28, and 31-40 (1000℉ limit) TC's 18-19, 28, and 31-40 did not exceed their 1000℉ limit. PASS
TC's 49-54 (500℉ above ambient) TC's 49-54  did not exceed  500℉ above their ambient temperatures. PASS
TC's 55-67 (750℉ above ambient) TC's 55-67 did not exceed  750℉ above their ambient temperatures. PASS

NFPA 285 Test Progress Pictures

We are in Social

TEST REQUIREMENTS TEST RESULTS PASS/FAIL
Flames did not reach 10 ft. above the window opening header. Flames did not reach 10 ft. above the window opening header. PASS
Flames did not reach a lateral distance of 5 ft. from the vertical centerline. Flames did not reach a lateral distance of 5 ft. from the vertical centerline. PASS
Flames did not propagate beyond the limits of the first story test room. Flames did not propagate beyond the limits of the first story test room. PASS
TC's 11 and 14-17 (1000℉ limit) TC's 11 and 14-17 did not exceed their 1000℉ limit. PASS
TC's 18-19, 28, and 31-40 (1000℉ limit) TC's 18-19, 28, and 31-40 did not exceed their 1000℉ limit. PASS
TC's 49-54 (500℉ above ambient) TC's 49-54  did not exceed  500℉ above their ambient temperatures. PASS
TC's 55-67 (750℉ above ambient) TC's 55-67 did not exceed  750℉ above their ambient temperatures. PASS